Commissioning

Select control interface (operating mode)

6

l

155

EDBCSXP064 EN 8.0

6.10

Select control interface (operating mode)

The control interface between master control (PLC) and ECS drive system serves to...

ƒ

control the drive;

ƒ

control the positioning sequence;

ƒ

transfer setpoints and actual values.

Process data are cyclically transmitted from the higher−level control (PLC) to the drive via
the control interface and the drive sends process data back to the control.

You can select from the following fieldbus interfaces under C4010:

ƒ

Automation interface (AIF) X1 for fieldbus communication modules
– C4010 = 2: 4 process data words with parameter data channel
– In conjunction with the EMF2192IB EtherCAT communication module,

sync−controlled via the terminal X6/DI1.

ƒ

MotionBus (CAN) connection X4
– C4010 = 0: CAN process data object 1 (PDO1, sync−controlled)
– C4010 = 5: CAN process data object 3 (PDO3, cyclic)

ƒ

System bus (CAN) connectionX14
– C4010 = 1: CAN−AUX process data object 1 (PDO1, sync−controlled)
– C4010 = 4: CAN−AUX (PDO2, cyclic)

The GDC contains the code C4010 in the parameter menu under Short setup

W

Control/Operating mode.

ECSXA442

Fig. 6−25

GDC view: Select short setup − operating mode