Commissioning

Starting positioning profiles (ProfEnable, profile number)

Start of positioning profile via the "ProfEnable" control bit

6

l

227

EDBCSXP064 EN 8.0

6.19.1

Start of positioning profile via the "ProfEnable" control bit

Preconditions

ƒ

The ECSxP axis module must be ready for starting. ( Controller is enabled, "Stand−by"
state is active, no fault, etc.)

ƒ

The master control (PLC) including the communication channels are ready to control
the axis module.

Control sequence

1. PLC:

Note: In order that the rising edge at Ctrl1.ProfEnable can be recognised by the ECSxP
axis module for starting the next profile, ensure that Ctrl1.ProfEnable= 0 in the axis
module.
– Select positioning profile number via the 4 control bits PNoSet_x in the control

word Ctrl1 (binary coded).

– Start the positioning profile by setting the control bit Ctrl1.ProfEnable to 1 (rising

edge).

2. ECSxP axis module:

ð Status bits Stat1.InTarget and Stat1.DwellTime are reset and the selected profile
number is accepted (display in Stat1.PNoAct_x).

3. PLC:

– Wait until the selected positioning profile has been started in the ECSxP axis

module.
Display: Status bits Stat1.PNoAct_x, Stat1.InTarget = 0, Stat1.DwellTime = 0).

4. PLC:

– Wait until the profile function has been processed or positioning has been

completed.
Display: Status bits Stat1.InTarget = 1 and Stat1.DwellTime = 1.

5. PLC:

– Reset control bit: Ctrl1.ProfEnable = 0

6. Proceed with step 1 for the next profile.