Configuration

Configuring MotionBus/system bus (CAN)

Setting CAN node address and baud rate

8

l

267

EDBCSXP064 EN 8.0

8.1.1.1

Settings via DIP switch

ECS_COB005

Fig. 8−2

DIP switch for node address and baud rate (all switches: OFF)

Node address setting

The node address is set by means of switches 2 ... 7 of the DIP switch. Specific values are
assigned to the switches. The sum of the values specifies the node address to be set (see
example).

Switch

Value

Example

Switching status

Node address

ON

OFF

ON

1

6

2

7

4

3

8

5

91

0

S1

OFF: Node address setting is only valid for CAN
(C0350 is overwritten if one of switches S2 ... S7
is in ON position.)
ON: Node address setting is valid for CAN and
CANaux (C0350 and C2450 are overwritten if
one of switches S2 ... S7 is in ON position.)

S2

32

ON

32 + 16 + 8 = 56

S3

16

ON

S4

8

ON

S5

4

OFF

S6

2

OFF

S7

1

OFF