Commissioning

Commissioning steps (overview)

Setting absolute positioning/relative continuous positioning

6

l

123

EDBCSXP064 EN 8.0

6.4.5

Setting absolute positioning/relative continuous positioning

)

Note!

ƒ

Absolute positioning is required for operation with a linear positioning axis.

ƒ

Relative positioning in the continuous measuring system is required for
operation with a continuous positioning axis.

ƒ

Comply with the commissioning steps in the given order!

Operation with a continuous positioning axis

Operation with a linear positioning axis

1.

Definition of positioning profile with relative
positioning in the continuous measuring system.
(

^ 191)

Set the following codes in the GDC parameter menu
in Positioning profiles

W Profile 02:

l

C3095/2 = 1 (positioning profile mode "modulo
pos.")

Definition of positioning profile with absolute
positioning. (

^ 191)

Set the following codes in the GDC parameter menu
in Positioning profiles

W Profile 02:

l

C3095/2 = 0 (positioning profile mode "absolute
pos.")

l

C3100/2 (position for positioning profile 2)

l

C3200/2 (speed for positioning profile 2)

l

C3300/2 (acceleration for positioning profile 2)

l

C3400/2 (deceleration for positioning profile 2)

2.

Enable controller. (

^ 241)

l

Press the <F8> key in the GDC.

l

Green LED is lit continuously if X6/SI1 = HIGH, X6/SI2 = HIGH, and the controller has been enabled via
the master control (PLC).

l

Green LED is blinking if X6/SI1 = HIGH and X6/SI2 = HIGH. (No enable via master control!)

3.

Start positioning profile (profile 02).

Set the following codes in the GDC parameter menu in Short setup

W Operating mode:

l

C4010 = 3 (control interface C4040)

l

C4040/Bit 5 = 1 (control bit Ctrl1.PNoSet_2, select positioning profile)

l

C4040/bit 8 = 1 (control bit Ctrl1.ProfEnable, start positioning profile)

ð Changeover to the "Positioning" state

– C4045/bit 4 = 1 (status bit Stat1.PStatPos)
– C4045/Bit 10 = 1 (status bit Stat1.ProfileBusy)

(Control bits see

^ 158, status bits see^ 161)

The drive travels the relative distance specified
under C3100/2.

The drive approaches the absolute target position
defined by C3100/2.

4.

Reset positioning profile (profile 02).

Settings:

l

C4040/bit 5 = 0

l

C4040/bit 8 = 0

ð Changeover to the "Stand−by" state

– C4045/Bit 0 = 1 (status bit Stat1.PStatStdBy)
– C4045/Bit 4 = 0 (status bit Stat1.PStatPos)
– C4045/Bit 14 = 1 (status bit Stat1.InTarget)
– C4045/Bit 15 = 1 (status bit Stat1.DwellTime)

Note:
To traverse a positioning profile with relative
positioning in the continuous measuring system
again, repeat steps 3. and 4.

Note:
To retravel a positioning profile with absolute
positioning,

l

change the value in C3100/2 (see step 1.);

l

then continue with steps 3. and 4.