Appendix – Lenze ECSCPxxx User Manual

Page 430

Advertising
background image

Appendix

Communication with MotionBus/system bus (CAN)
Addressing of the parameter and process data objects

12

l

430

EDBCSXP064 EN 8.0

Assignment of the node address for the data exchange between Lenze devices

If Lenze devices are assigned with node addresses in a complete ascending order, the
identifiers of the event−controlled data objects (CAN2_IO/CAN3_IO) are factory−set so
that the devices are able to communicate with each other.

L

Node-ID 1

CAN2_OUT

CAN2_IN

CAN3_OUT

CAN3_IN

L

Node-ID 2

CAN2_OUT

CAN2_IN

CAN3_OUT

CAN3_IN

L

Node-ID 3

Fig. 12−10

Data exchange between Lenze devices

Assign each node within the system bus network to a node address ˘ also called node ID
˘ for a clear identification in the range 1 to 63.

ƒ

A node address may not be assigned more than once within a network.

)

Note!

The "8.1.1 Setting of CAN node address and baud rate" chapter contains
information on

ƒ

Setting of the node address (

266).

ƒ

Individual addressing (

271).