Configuration

Configuring MotionBus/system bus (CAN)

Defining boot−up master in the drive system

8

l

273

EDBCSXP064 EN 8.0

8.1.3

Defining boot−up master in the drive system

If the bus initialisation and the related state change from "Pre−Operational" to
"Operational" is not carried out by a higher−level host system (PLC), another node can be
determined as boot−up master to carry out this task.

The master functionality only is required for the initialisation phase of the drive system. A
boot−up time for the master in the initialisation phase can be set via C0356/C2456
(

274).

By means of the NMT telegram start_remote_node (broadcast telegram) all nodes are
shifted to the NMT−state "Operational" by the master. A data exchange via the process
data objects can only be effected in this state.

Use C0352/C2452 for configuration.

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0352 CAN mst

0

Boot−up master/slave
configuration for CAN bus
interface X4

^ 273

0

Slave

1

Master boot−up

Device is active as CAN boot−up
master.

2

Master node guarding

3

Slave heartbeat producer

4

Slave node guarding

C2452 CANa mst

0

Configuration of master/slave
for CAN bus interface X14
(CAN−AUX)

^ 273

0

Slave

1

Master

Save changes with C0003 = 1.

The settings are only accepted after carrying out one of the following actions:

ƒ

Renewed switch−on of the 24 V low−voltage supply

ƒ

Reset node via the bus system (by the network management (NMT))

ƒ

Variable CAN_bResetNode_b or CANaux_bResetNode_b = TRUE

ƒ

Reset node with C0358/2458 = 1

)

Note!

If reset node is executed via GDC, communication will be interrupted. You
therefore have to log in again manually or find the devices connected to the
bus once again (fieldbus scan).