Malfunction of the drive

Maloperation/fault

Cause

Remedy

Feedback system

l

Motor rotates CCW when viewed
to the motor shaft.

l

C0060 counts down after
controller enable.

Feedback system is not connected in
correct phase relation.

Connect feedback system in correct
phase relation.
The rotor position indicated under
C0060 is derived from the position
encoder (MCTRL_dnPos_p).
Therefore observe the mounting
position when using separate
feedback systems for position
(C0490) and speed (C0495).

Asynchronous motor

l

Motor rotates with I

max

and half

slip frequency.

l

Motor does not react to setpoint
change.

Motor is not connected in correct
phase relation.

Connect motor in correct phase
relation at the terminals U, V, W.

Synchronous motor

l

Motor does not follow the
setpoint change.

l

I

max

follows the setpoint

selection in idle state.

Motor is not connected in correct
phase relation.

Connect motor in correct phase
relation at the terminals U, V, W.

l

Motor rotates CCW when viewed
to the motor shaft.

l

Synchronous motor accelerates
with a speed setpoint = 0 to
rated speed.

l

Torque of synchronous motor is
too low.

Rotor angle (offset of electrical and
mechanical rotor angle) is not
correct.

Carry out rotor position adjustment
(C0095 = 1) or set rotor
displacement angle manually.
Operate motor without load for this
purpose!

l

Motor blocks in certain positions. The number of pole pairs of the

resolver or motor is not set
correctly.

Number of pole pairs (C0080) must
be set correctly.