Appendix – Lenze ECSCPxxx User Manual

Page 379

Advertising
background image

Appendix

Code table

12

l

379

EDBCSXP064 EN 8.0

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C0559 SD8 filter t

1

Filter time constant (SD8)

1

{1 ms}

200 Example:

If the setting is "10 ms", a
SD8−TRIP is actuated after 10 ms.

C0576 nErr tolerance

100

Tolerance window for the speed
system deviation referring to
n

max

100 % = lowest monitoring
sensitivity

^ 321

0

{1 %}

100

C0577 Vp fld weak

0.100

Gain of the field weakening
controller (V

p

)

^ 254

0.000

{0.001}

63.999

C0578 Tn fld weak

3.0

Integral−action time of the field
weakening controller (V

n

)

0.1

{0.1 ms}

6000.0

C0579 nErr response

3

Fault response − monitoring of
speed system deviation

^ 321

0

TRIP

1

Message

2

Warning

3

Off

4

FAIL−QSP

C0580 Monit SD8

3

Fault response − monitoring of
SinCos signals at X8

^ 320

0

TRIP

3

Off

C0581 MONIT EEr

0

Fault response − external fault
monitoring "ExternalFault" (EEr)

0

TRIP

1

Message

2

Warning

3

Off

4

FAIL−QSP

C0582 MONIT OH4

2

Setting of the fault response −
monitoring of heatsink
temperature in C0122

^ 303

0

TRIP

2

Warning

3

Off

C0583 MONIT OH3

0

Fault response − monitoring of
motor temperature (fixed
temperature threshold).
Detection through KTY thermal
sensor via resolver input X7 or
encoder input X8.

^ 301

0

TRIP

2

Warning

3

Off