Appendix

Code table

12

l

382

EDBCSXP064 EN 8.0

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C0605 MONIT OH5

2

Fault response − monitoring of
temperature inside the
controller.
Temperature threshold can be
set under C0124.

^ 304

0

TRIP

2

Warning

3

Off

C0606 MONIT OC8

2

Fault response − monitoring of
I

2

x t motor utilisation.

Threshold can be set under
C0120.

^ 309

0

TRIP

2

Warning

3

Off

C0607 MONIT NMAX

0

Fault response − maximum speed
monitoring of the machine

0

TRIP

2

Warning

3

Off

C0608 ovr. Tx−Queue

2

Fault response − transmission
memory overflow of free CAN
objects

0

TRIP

1

Message

2

Warning

3

Off

4

FAIL−QSP

C0609 ovr. Rx−Isr

0

Fault response Receive memory
overflow of free CAN objects

0

TRIP

4

FAIL−QSP

C0855

Digital process data input words
are indicated on the AIF interface
(AIF1_IN)
Hexadecimal value is bit−coded.
Read only

1 AIF1 IN bits

0000

{hex}

FFFF Input word 2 (bit 0 ... 15)

2 AIF1 IN bits

Input word 3 (bit 0 ... 15)

C0856

Analog process data input words
are indicated decimally on the
AIF interface (AIF1_IN)
100.00% = 16384
Read only

1 AIF1 IN words

−199.99

{0.01 %}

199.99 Input word 1

2 AIF1 IN words

Input word 2

3 AIF1 IN words

Input word 3

C0857 AIF1 IN phi

32 bits of phase information on
the AIF interface (AIF1_IN)
Read only

−2147483648

{1}

2147483647