Commissioning

Entry of machine parameters

6

l

167

EDBCSXP064 EN 8.0

IMPORTANT

Possible settings

Code

Selection

Lenze/
{Appl.}

Designation

No.

C3035 DwellTime

50

Dwell time after end of profile

^ 232

0

{1 ms}

65535 Time required from positioning

profile end (setpoint generator
has reached target position) to
the setting of status bit
Stat1.DwellTime = 1

C3036 BounceTime

0

Debounce time for touch probe
input

0

{0.001 ms}

65535

C3040 SW−LimPos

3600.0

Positive software limit position

^ 237

0.0000

{0.0001

units}

214000.0000

C3041 SW−LimNeg

−3600.0

Negative software limit position

^ 237

−214000.0000

{0.0001

units}

0.0000

C4018 MmaxVal

100.0

Limit value for max. torque
(M

max

)

0.01

{0.01 %}

100.00

l

100 % = maximum torque
from C0057

l

The value in C4018 is
overwritten by the following
functions:

– Torque limitation after

positioning

^ 208

– Homing modes 14 and 15

(C3010)

^ 186

C4060 ES_NOffs

Only for "electrical shaft"
function: default value (in
increments) for
speed−proportional angular
trimming relating to
15000 rev./min.
Note: Only change value when
the controller is at standstill!

^ 235

−655360

{1 inc}

655360