3] list of pio signals – IAI America ERC3 User Manual

Page 106

Advertising
background image

Chapter 3 Wiring

3.1 Positioner Mode 1 (Standard

Type)

96

[3] List of PIO Signals

The table below lists the functions of PIO signals. Refer to the section shown in Relevant

Sections for the details of the control of each signal.

Category

Signal

Abbreviation

Signal Name

Function Description

Relevant

Sections

EMG

Emergency Stop Input It shuts the motor power supply.

4.2.2 [3]

BK

Brake Forcible Release The brake will forcibly be released.

4.2.2 [4]

CSTR

Start Signal

The actuator will start to move to the position set by the

command position number.

4.2.2 [7]

PC1 to PC8 Command Position

Number

Input of the position number to move (binary input)

4.2.2 [7]

*STP

Pause

When this signal turns OFF while the actuator is moving,

the actuator will decelerate to stop. The remaining

movement is retained and will resume when the signal is

turned ON again.

4.2.2 [7]

HOME

Home Return

The controller will perform home return operation when

this signal is turned ON.

4.2.2 [6]

Input

ST0 to ST6 Start Signal

The actuator moves to the position corresponding to the

start signal when this signal is on in Electromagnetic

Valve Mode.

4.2.2 [8]

PEND

Position Complete

Turns ON in the positioning width range after actuator

operation. The INP signal will turn OFF if the position

deviation exceeds the in-position range. PEND and INP

can be switched over by the parameter.

4.2.2 [6] [7]

HEND

Home Return

Completion

This signal will turn ON when home return has been

completed.

It will be kept ON unless the home position is lost.

4.2.2 [6] [7]

ZONE1

Zone Signal 1

Turns ON if the current actuator

position is within the range set to the

parameter No.1, 2.

4.2.2 [6]

PZONE

Position Zone

This is a function belonging to the

commanded position number, and the

zone range is to be set in the position

table and is effective only when that

position is indicated. This signal turns

ON when the current position comes

into the range set in the position data.

For PIO Pattern 2,

the mode can be

switched over

between ZONE1

and PZONE with

Parameter No.

149.

(At the delivery:

PZONE)

4.2.2 [6]

*ALM

Alarm

Turns ON when the controller is in normal condition, and

turns OFF when an alarm is generated.

4.2.2 [6]

Output

PE0 to PE2 Current Position

Number

In the electromagnetic valve mode, this signal will turn

ON when the actuator completes moving to the target

position.

4.2.2 [8]