Chapter 7 troubleshooting 7.4 alarm list – IAI America ERC3 User Manual

Page 377

Advertising
background image

Chapter 7

Troubleshooting

7.4
Alarm List

367

Alarm

Code

Alarm

Level

Alarm Name

Cause/Treatment

Positioner

Mode 1

Pulse

Train

Control

Mode

Positioner

Mode 2

MEC

Mode 1

MEC

Mode 2

0BE

Home return

timeout

Cause

: Home return does not complete after

elapse of a certain period after the

start of home return.

Treatment : This error does not occur in normal

operation. Please contact IAI.

{

{

{

{

0C0

Actual speed

excessive

Cause

: This indicates the number of motor

rotation exceeded the number of

allowable rotation.

1) The slide resistance of the actuator

is locally high.

2) The load is increased too much due

to a external force.

With the reasons above, it can be

considered a sudden speed

increase has occurred before

detecting the servo error.

Treatment : Even though this would not occur in

normal operation, check if there is any

abnormality in the parts assembly

condition. Also check if there is a

possibility that an external force may

be applied in the direction of the

actuator movement.

{

{

{

{

0C1

Oper

ation releas

e

Servo error

Cause

: It indicates 2 seconds has passed

without making a move since a move

command was received.

1) Connection error or wire breakage

of motor/encoder cables.

2) Brake is not released (when

equipped with a brake).

3) Load to the motor is high due to

external force.

4) The resistance in the actuator

sliding operation is large.

Treatment : 1) Check for the motor/encoder cable

wiring condition.

2) For Positioner Mode 1 and MEC

Mode 1, if the problem is solved

with 24V DC 150mA being supplied

to BK, it may be concerned a

malfunction of the controller inside

the ERC3 motor unit.

3) Confirm that there is no error in the

mechanical part assembly

condition.

4) If the loaded weight is within the

allowable range, turn the power off

and check the resistance in sliding

operation by moving the slider with

hand.

{

{

{

{

0C8

Overcurrent

Cause

: The output current in the power circuit

section is increased abnormally.

Treatment : This alarm will not be generated in

normal operation. There may be

concerned a degradation of motor

winding insulation, malfunction of the

controller inside the ERC3 motor unit,

etc. Please contact IAI.

{

{

{

{

0C9

C

ol

d s

ta

rt

Overvoltage

Cause

: The power voltage reached the

overvoltage.

Treatment : There may be concerned a

malfunction of a component of the

controller inside the ERC3 motor unit.

Please contact IAI.

{

{

{

{