Chapter 3 Wiring

3.3 Positioner Mode 2 (Extension

Type by PIO Converter)

114

3.3.3 Circuit Diagram

Sample circuit diagrams are shown below.



[1] Power Line and Emergency Stop Circuit

(1) Built-in Drive Cutoff Relay Type

Note 1 When the teaching pendant is not connected, S1 and S2 become short-circuited inside the

controller.

Note 2 For CR1, select the one with coil current 0.1A or less.

Note 3 This circuit is equivalent to Safety Category 1.

The load current for the emergency stop signal EMG (-) to turn ON/OFF at contact CR1 is 24V

DC and 20mA.

Caution:

• Do not attempt to cut the 0V circuit of GND whit the emergency stop. Doing so may burn the

internal circuit. If an absolute shutoff of the power supply is required, conduct it on the primary

side of DC power supply (alternating current side).

• In case the power source for each controller is different, join the 0V of each power supply

together.

CR1

(Note 2)

CP24V

GND

S2

MPI
MPO

EMG (-)

Emergency-stop

switch on the teaching

pendant

Motor power

supply

PIO Converter

CR1

(Note 3)

Emergency stop

reset switch

Emergency

stop switch

CR1

S1

S2

S1

S2

S1

PIO Converter

1st unit

24V

0V

PIO Converter

2nd unit

(Note 1)

Control

power supply

PIO

Converter

2nd unit

PIO

Converter

Nth unit

Emergency

stop signal

ERC3

Drive cutoff relay

EMG (-)

MPI
MPO

CP24V

PIO Converter

Nth unit

EMG (-)

MPI
MPO

CP24V

GND

GND