Chapter 4 Operation

4.2 Operation in Positioner Mode

4.2.2 Operation in Positioner Mode 1

174














If there is a problem in this operation, have an interlocking to the start signal by the home-return complete

signal HEND since there is the home-return signal HOME in PIO Pattern 1.

There is no home-return signal in PIO Pattern 2. Therefore, it is necessary to set 0.00mm to one of the

position numbers as a position for positioning, and perform positioning to that position. The actuator

performs positioning to the home position and the home-return complete signal HEND turns ON. Interlock

the setting so positioning cannot be conducted at other positions by the home-return complete signal

HEND.

„

Binary data

{

: ON z : OFF

Command position No. PC8

PC4

PC2

PC1

0

z

z

z

z

1

z

z

z

{

2

z

z

{

z

3

z

z

{

{

4

z

{

z

z

5

z

{

z

{

6

z

{

{

z

7

z

{

{

{

8

{

z

z

z

9

{

z

z

{

10

{

z

{

z

11

{

z

{

{

12

{

{

z

z

13

{

{

z

{

14

{

{

{

z

15

{

{

{

{

Command position No.

PC1 to PC*

(PLCψController)䎃

Start signal CSTR

(PLCψController)䎃

䎷䎔

t

䎙䏐䏖

Turned OFF by

turning PEND OFF

Positioning Completion Signal

PEND

(ControllerĺPLC)

Turned ON

after entering

into positioning

width zone

Target Position

Home return complete signal

HEND

(ControllerψPLC)

This signal will turn ON when

home return has been completed.

Positioning

Home return