Chapter 4 Operation

4.2 Operation in Positioner Mode

4.2.3 Operation in Positioner Mode 2 (Operation Using PIO Converter)

227

„

Control method

1) When start signal ST* is turned ON, the actuator starts acceleration based on the data in

the specified position table for positioning to the target position.

2) For PIO converter, when the positioning is finished, the positioning complete signal PEND

turns ON at the same time as Current Position No. PE* of the commanded position.

3) For PIO converter, turn OFF ST* Signal once PEND Signal is turned ON.

4) Current position No. PE* and positioning completion signal PEND are turned ON if the

remaining moving distance is entered into the positioning width zone. Once Current

Position No. PE* and PEND Signal are turned ON, they remain ON unless the start signal

ST* is turned ON or the servo is turned OFF. They would not turn off even out of the

positioning width range.

(Note 1)

Note 1 A switchover is available to INP (Setting 1) in Parameter No.39. PEND becomes an

in-position signal that turns OFF out of the positioning width.

 

Caution: (1) If the ST* signal is turned ON for the position after completion of

positioning, both the PE* and PEND signals remain ON (except the

pitch feed operation).

(2) Both the PE* and PEND signals are set to ON in the positioning

width zone. Accordingly, they may be turned ON under operation of

the actuator if a large positioning width is set.

(3) Interlock should be taken so that two or more ST* signals are set to

ON simultaneously.

1) Entering the ST* signal of another position during positioning is

invalid. If the ST* signal of another position is turned ON during

positioning, the operation is terminated after the completion of

the positioning being operated.

2) Entering the ST* signal of another position with the ST* signal of

the current position remaining ON after the completion of

positioning allows the positioning to the other position to be

executed.

(4) If Parameter No.27 “Move command type” is set to “0” (factory

setting), turning ST* OFF during positioning caused the operation to

be interrupted.

Start signal

ST*

(PLCoController)

Positioning Completion Signal

PEND

(ControlleroPLC)

Turned ON after

entering into

positioning width zone

Target Position

Current Position No.

PE*

(ControlleroPLC)

Turned OFF by

turning PE* ON