Chapter 6

Adjustment of Operation

6.3 I/O Parameter

6.3.1 Positioner Mode 1, Positioner Mode 2 and Pulse

Train Control Mode

314

(15) Home return offset level (Parameter No.22)

No.

Name

Symbol

Unit

Input Range

Default factory setting

22 Home return offset level

OFST

mm

0.00 to 9999.99

In accordance with

actuator

In this setting can set the distance from the mechanical end to the home position.

An adjustment is available for the following cases.

1) Want to match the actuator home position and the mechanical origin of the system.

2) Want to set a new home after reversing the factory-set home direction.

3) Want to eliminate a slight deviation from the previous home position generated after

replacing the actuator.

[Adjustment Process]

1) Homing execution

2) Offset check

3) Parameter setting change

4) After the setting, repeat home return several times to confirm that the actuator always

returns to the same home position.

Caution : x Soft limit takes the home position as the datum. Therefore, when a change

is made to the value of home-return offset level, also revise the value for

soft limit.

x

If the home return offset has been changed, the soft limit parameters must

also be adjusted accordingly.

Do not set a smaller value than the initial setting value for Home Return

Offset. Normal excitation detection cannot be performed, and there may be

a risk of generating the excitation detection error or causing abnormal

noise.

In case the there is a necessity of setting a value less than the initial

setting, contact IAI.