Chapter 4 Operation

4.2 Operation in Positioner Mode

4.2.3 Operation in Positioner Mode 2 (Operation Using PIO Converter)

197

4.2.3 Operation in Positioner Mode 2 (Operation Using PIO Converter)

To perform an operation of Position Mode 2, PIO Converter (option) is necessary. By using PIO

Converter, an operation with extended function of ERC3 is available.

It is available to select 6 types of PIO patterns with the parameters. This PIO Pattern cannot be

switched over after the system is finished to be established or during the actuator operation.

Choose the optimum pattern beforehand considering the system operation specifications and

prepare the cables and sequence design.

[1] PIO Pattern Selection and Main Functions

{

: Valid function

PIO Pattern

(Parameter No.25)

0

1

2

3

4

5

Mode

Positioning

mode

Teaching

mode

256-point

mode

512-point

mode

Solenoid

valve

mode 1

Solenoid

valve

mode 2

Number of positioning

points

64

64

256

512

7

3

Operation with the

Position No. Input

{

{

{

{

u

u

Position No. direct

command operation

u

u

u

u

{

{

Positioning

{

{

{

{

{

{

Velocity change during

the movement

{

{

{

{

u

u

Pressing (tension)

{

{

{

{

{

u

Pitch feeding

(relative moving feed)

{

{

{

{

{

u

Home return signal input

{

{

{

{

{

u

Pause

{

{

{

{

{

ٌ

(Note 1)

Jog moving signal

u

{

u

u

u

u

Teaching signal input

(Current position writing)

u

{

u

u

u

u

Brake release signal input

{

u

{

{

{

{

Moving signal output

{

{

u

u

u

u

Zone signal output

{

u

u

u

{

{

M

aj

or

fu

nc

tio

ns

Position zone signal

output

{

{

{

u

{

{

(Note 1) The pause signal is not provided. [Refer to 4.2.3 [8] (5).]

(Reference)

Zone signal output signal : The zone range is set to the Parameters No.1 and 2 and No.23

and 24, and becomes always effective after the home return is

complete.

Position zone signal

: This feature is associated with the specified position number. The

zone range is set in the position table. The zone range is enabled

only when the position is specified but disabled if another position

is specified.