12] commanded position no. output circuit, 13] start signal output circuit – IAI America ERC3 User Manual

Page 429

Advertising
background image

Chapter 10

Appendix

10.5
Example of Basic Positioning Sequence

(PIO Patterns 0 to 3 in PIO Converter)

419

[12] Commanded Position No. Output Circuit

Depending on the result of the ready circuit, this circuit converts position No. to the binary code

and outputs the data from PLC to ERC3 and PIO converter.

156

OUT8

PC1

Command Position 1

AUX18

Position 1

Set

AUX20

Position 3

Set

AUX20

Position 3

Set

159

OUT9

PC2

Command Position 2

AUX19

Position 3

Set

[Position No.1]

[Position No.2]

[Position No.3]

[13] Start Signal Output Circuit

After 20msec from the output of position No., this circuit outputs the start signal from PLC to

ERC3 and PIO converter.

162

166

AUX9

Auxiliary

Position 1

Positioning

Start

AUX12

Auxiliary

Position 2

Positioning

Start

AUX15

Auxiliary

Position 3

Positioning

Start

OUT13

CSTR

Waiting for start

Start

<Timer 5 (bit)>

a116

Waiting for Start

TIM5

200ms

is set to

TIM5

20msec

Set this signal to be 2 to 4 times as

long as PLC scanning time so that it

is turned ON after position No. is output

securely. (The ERC3 and PIO converter

input condition is defined to turn the signal

ON after 6msec.)

Each of 2 , 5 , and 8 signals is turned OFF if the actuator is

started by start signal. It is because PEND it turned OFF to turn

the moving circuit, a main circuit, ON. (Handshake)