Chapter 4 Operation

4.4 Operation in MEC Mode 1 and 2 (Operation with PLC)

265





T (before detecting excitation) = SON signal identification (6ms) + Excitation detection time (T1 +

T2) × Number of retry (10 times Max.) + Servo ON delay time (T3)

T (after detecting excitation) = SON signal identification (6ms) + Servo ON delay time (T3)

T1 : Parameter No.36

It differs depending on the setting of excitation detection type.

Set Value = 0

ĺ 160ms

Set Value = 1, 2 ĺ 220ms

T2 : Parameter No.35

Setting of excitation phase signal detection time

It is set to 10ms in the initial setting.

T3 : Fixed to 20ms

(Note) • Excitation detection operation of the motor is conducted at the first servo-on after the

power is turned ON.

• PEND would not turn ON if the pause signal *STP is OFF.

EMG or

EMG(-)

Servo

ON

Brake

Excitation

Lock

Release

T

26ms