7.4 Alarm List

Alarm

Code

Alarm

Level

Alarm Name

Cause/Treatment

Positioner

Mode 1

Pulse

Train

Control

Mode

Positioner

Mode 2

MEC

Mode 1

MEC

Mode 2

02C

Monitoring data

type change

command during

monitoring

Cause

: Changing data type was directed

during monitoring by the monitoring

function of PC software.

Treatment : Stop the monitoring before changing

data type.

{

{

Ч

Ч

02D

Monitoring

related

command in

monitoring

function invalid

status

Cause

: An attempt was made to perform

monitoring in the state where the

monitoring function is set to be

ineffective.

Treatment : Set parameter No.112 (Selection of

monitoring mode) to “1” or “2” (“0”: no

use).

{

{

Ч

Ч

02E

RTC related

command in

RTC invalid

status

Cause

: An attempt was made to use the

calendar in the state where the RTC

(calendar) function was made

ineffective.

Treatment : Set parameter No.111 (Selection of

use of calendar function) to “1” (“0”: no

use).

Ч

{

Ч

Ч

048

Driver overload

alarm

Cause

: There is a risk of overload with the

current operation condition.

Treatment : Lower the setting of

acceleration/deceleration. Also,

increase the frequency of pause.

{

{

{

{

04E

Exceeded

movement count

threshold

Cause

: In the case of Positioner Mode 2, the

total number of movement exceeded

the number set in Parameter No.147

“Threshold for Total Number of

Movement”.

In the case of MEC Mode 2, the total

number of movement exceeded the

number set in Parameter No.26

“Threshold for Total Number of

Movement”.

Ч

{

Ч

{

04F

M

es

sa

ge

Exceeded

operated

distance

threshold

Cause

: In the case of Positioner Mode 2, the

total distance of actuator drive

exceeded the number set in

Parameter No.148 “Threshold for Total

Distance of Drive”.

In the case of MEC Mode 2, the total

distance of actuator drive exceeded

the number set in Parameter No.27

“Threshold for Total Number of Drive”.

Ч

{

Ч

{

080

Oper

ation releas

e

Move command

in servo OFF

Cause

: A move command was issued when

the servo is OFF.

Treatment : 1) Positioner Mode 1, Positioner Mode

2, Pulse Train Control Mode

Issue a movement command after

confirming the servo is ON (servo

ON signal SV or position complete

signal PEND is ON).

2) MEC Mode 1, MEC Mode 2

Cancel the emergency stop if it is

not yet cancelled, and turn the

servo ON to make a movement

command.

{

{

{

{