3 alarm level – IAI America ERC3 User Manual

Page 371

Advertising
background image

Chapter 7

Troubleshooting

7.3
Alarm Level

361

7.3 Alarm Level

The alarms are classified to 3 types of levels by the content of the error.

Alarm level

ALM lamp

*ALM signal

Status when an

error occurred

Cancellation method

Message

(Note 1)

OFF

No output

No stop

Alarm of maintenance output such as

battery voltage drop or the teaching tool

such as PC software

[Refer to Instruction Manual of each tool

for details.]

Operation

release

ON

Output

Servo OFF after

deceleration to

stop

Reset the alarm by the PIO or teaching

tool.

Cold start

ON

Output

Servo OFF after

deceleration to

stop

Software reset or power reconnection by

teaching tool.

Home return is required for any actuators

of other than simple absolute

specification.

Caution: Reset each alarm after identifying and removing the cause.

If the cause of the alarm cannot be removed or when the alarm cannot be reset

after removing the cause, please contact IAI.

If the same error occurs again after resetting the alarm, it means that the cause of

the alarm has not been removed.

(Note 1) Set Parameter No.156 Torque Check/Light Malfunction Output, and the output is

made to PIO (OUT 15) when ERC3 or PIO converter gets to either of the following

conditions;

1) Warning for Absolute Battery Voltage Drop ····

Supply the power for 72 hours or more to charge the battery

sufficiently and then perform the Absolute Reset operation. If the

same failure occurs often even with enough battery charge, it is

considered the end of the battery life.

Replace the battery.

2) When satisfying the conditions to generate the message level alarm described in

(7.4) in the next page