Chapter 3 Wiring

3.3 Positioner Mode 2 (Extension

Type by PIO Converter)

109

3.3.2 PIO Pattern Selection and PIO Signal

[1] PIO Pattern (Control Pattern) Selection

PIO Converter can extend the positioner function of ERC3, and enables to have 6 types of

control methods. Set the suitable PIO pattern to Parameter No.25 “PIO Pattern Select”.

Check the 4.2.3 Operation in Positioner Mode 2 for the details of PIO Patterns.



Type

Value set in

parameter

No.25

Mode

Overview

PIO

Pattern 0

0

(at the

delivery)

Positioning

mode

(Standard type)

x

Number of positioning points : 64 points

x

Position command : binary code

x

Zone signal output

*1

: 1 point

x

Position zone signal output

*2

: 1 point

(Note 1)

PIO

Pattern 1

1

Teaching mode

(Teaching type)

x

Number of positioning points : 64 points

x

Position command : binary code

x

Position zone signal output

*2

: 1 point

(Note 1)

x

Writing current position data to position table

enabled by PIO signal

PIO

Pattern 2

2

256-point mode

(Number of

positioning

points :

256-point type)

x

Number of positioning points : 256 points

x

Position command : binary code

x

Position zone signal output

*2

: 1 point

(Note 1)

PIO

Pattern 3

3

512-point mode

(Number of

positioning

points :

512-point type)

x

Number of positioning points : 512 points

x

Position command : binary code

x

Zone signal output : None

PIO

Pattern 4

4

Solenoid valve

mode 1

(7-point type)

x

Number of positioning points : 7 points

x

Position command : Individual number signal ON

x

Zone signal output

*1

: 1 point

x

Position zone signal output

*2

: 1 point

(Note 1)

PIO

Pattern 5

5

Solenoid valve

mode 2

(3-point type)

x

Number of positioning points : 3 points

x

Position command : Individual number signal ON

x

Completion signal : Signal equivalent to LS

(limit switch) enabled

x

Zone signal output

*1

: 1 point

x

Position zone signal output

*2

: 1 point

(Note 1)

Note 1 The position zone signal output can be switched over to the zone signal output with the

setting of Parameter No.149.

*1 Zone signal output

: Zone range is to be set to either Parameter No.1, 2 and it is

always available after the home-return operation is complete.

*2 Position zone signal output : This feature is associated with the specified position number.

The zone range is set in the position table. The zone range is

enabled only when the position is specified but disabled if

another position is specified.