IAI America ERC3 User Manual

Page 97

Advertising
background image

Chapter 2 Installation

2.3 How to Install

87

(2) When controlling with using PIO converter

There is a terminal for frame grounding on the front panel of PIO Converter. Connect it to the

grounding terminal. Use a low carbon steel wire with the diameter 1.6mm (AWG14: 2mm

2

) or

more for grounding.

(3) How to ground Quick Teach

1) RCM-PST-0 (24V DC power supply type)

It is not necessary to ground the quick teach since its frame ground is connected to the actuator

with the connection cable. Have a ground on the platform to install the actuator the actuator main

unit. For grounding, make sure to conduct Class D Grounding (former Class 3 Grounding:

grounding resistance 100: or less).

PLC

PIO Converter

Copper Wire :

Connect to a ground cable with

diameter 1.6mm (AWG14: 2mm

2

)

or more.

Do not share the ground wire with or connect

to other equipment. Ground each controller.

PIO Converter

Other

equipment

PIO Converter

Other

equipment

Other

equipment

Earth Terminal

Class D grounding

(Formerly Class-III grounding :

Grounding resistance at 100: or less)