IAI America ERC3 User Manual

Page 267

Advertising
background image

Chapter 4 Operation

4.3
Operation in Pulse

Train Control Mode (How to Operate

Pulse

Train Control

Type)

257

[9] Parameter Settings Required for Advanced Operations

Depending on systems and/or loads, set the following parameters if necessary.

(1) Position command primary filter time constant

No.

Name

Symbol

Unit

Input

Range

Initial

Value

55

Position command primary

filter time constant

PLPF

msec

0.0 to

100.0

0.0

The acceleration/deceleration of the actuator can be set in S-shaped curve with this parameter

setting. (It is not the S-shaped acceleration/deceleration function.)

If command pulse train is input at a certain frequency, the actuator is accelerated/decelerated

slowly depending on the time constant.

The actuator moves by the number of command pulses.

Even if the host controller (PLC etc.) has no acceleration/deceleration function or the

frequency of command pulses varies rapidly, the actuator can be accelerated/decelerated

smoothly.

The delay in positioning stabilizing time requires approximately 3 times longer than the set

value after the command pulse input stop. If the set value is 100ms, the stabilizing time would

be approximately 300ms.

Pulse Train

Velocity

(2) Torque Limit

No.

Name

Symbol

Unit

Input

Range

Initial

Value

57

Torque Limit

TQLM

%

0 to 70

70

Set a desired torque limit used in the torque limit input signal TL, which is an external input

signal.

Set the torque in % to the rated thrust (rated current).

[Refer to 1.2.1 [6] Current Limit Value and Pressing Force]

When the torque limit signal TL of the external input signal is turned ON, current limitation

corresponding to the setting is applied.

When the torque current of the motor reaches the set value, the torque limiting signal TLR of

the external output signal is output.

(3) Clearing deviation during servo OFF or alarm stop

No.

Name

Symbol

Unit

Input

Range

Initial

Value

58

Clearing deviation during servo OFF

or alarm stop

FSTP

0 to 1

1

It can be selected whether to valid or invalid the deviation clear at the servo-off or an alarm

stop.

0: Disable

1: Enable