Chapter 3 Wiring

3.3 Positioner Mode 2 (Extension

Type by PIO Converter)

113

Category

Signal

Abbreviation

Signal Name

Function Description

Relevant

Sections

PEND/INP Position Complete

Turns ON in the positioning width range after actuator

operation. The INP signal will turn OFF if the position deviation

exceeds the in-position range. PEND and INP can be switched

over by the parameter.

4.2.3 [6], [7]

PM1 to

PM256

Completion Position

No.

The position No. reached after the positioning completion, is

output (binary output).

4.2.3 [6]

HEND

Home Return

Completion

This signal will turn ON when home return has been completed.

It will be kept ON unless the home position is lost.

4.2.3 [5]

ZONE1

ZONE2

Zone

Turns ON if the current actuator position is within the range set

to the parameter.

4.2.3 [5]

PZONE Position Zone

This signal will turn ON when the current actuator position

enters the range specified the position data after position

movement. Even though it can be used together with ZONE1,

PZONE will become only available for operation by the set

position number.

4.2.3 [5]

*ALM

Alarm

Turns ON when the controller is in normal condition, and turns

OFF when an alarm is generated.

4.2.3 [5]

ALM1 to

ALM8

Alarm Code

The detail of the alarm is output with binary code when an

alarm more than the operation cancel level is issued.

4.2.3 [5]

MOVE

Moving

Turns ON during the actuator is moving (including home-return

operation and pressing operation).

4.2.3 [6]

SV

Servo ON

This signal will remain ON while the servo is ON.

4.2.3 [5]

*EMGS

Emergency Stop

Output

This signal remains ON while the controller is under the

emergency stop reset condition and turns OFF when the

emergency stop condition is enabled. (Regardless of alarms.)

4.2.3 [5]

MODES Teaching Mode Output

This signal will turn ON while the teaching mode is enabled by

the input of the MODE signal and will turn OFF when the mode

changes to the normal mode.

4.2.3 [6]

WEND

Writing Complete

This is a signal effective while in Teaching Mode, and is turned

ON when the writing by PWRT signal is complete, and turned

OFF at the same time as PWRT signal is turned OFF.

4.2.3 [6]

PE0 to PE6 Current Position

Number

In the solenoid valve mode, this signal will turn ON when the

actuator completes moving to the target position.

4.2.3 [7]

LS0 to LS2 Limit Switch Output

Turns ON when the current actuator position is within the range

of positioning width (r) of the target position. It is output even

before the movement command and the servo is OFF if the

home-return operation is completed.

4.2.3 [8]

Output

*ALML

Light Error Output

Outputs when a message level alarm is generated.

(It is necessary to set parameter)

It is ON in the normal condition, and turned OFF when an alarm

is issued.

4.4

Signal with “*” expresses the signal of active low. The controller executes the command when the input signal is OFF. The

output should normally be ON in a condition that the power is supplied and OFF in the signal output.