Chapter 4 Operation

4.2 Operation in Positioner Mode

4.2.3 Operation in Positioner Mode 2 (Operation Using PIO Converter)

232

Judging completion of pressing operation

The torque (current limit value) set in % in “Pressing” in the position table, and turns ON the

pressing complete signal PEND when the load current reaches the following condition. PEND

is turned ON at satisfaction of the condition if the work is not stopped. It is the same for PE*.

(Accumulated time in which current reaches pressing value [%]) – (accumulated time in which

current is less than pressing value [%]) • 255ms (Parameter No.6)

Current

Time

Pressing [%]

Operation

start

Approach end

Pressing start

200ms

20ms

75ms

295ms

200ms + 75ms – 20ms • 255ms

Pressing Completion (PEND Output)

Contacting work

Decrease in current due to movement of work