Chapter 4 Operation

4.3
Operation in Pulse

Train Control Mode (How to Operate

Pulse

Train Control

Type)

249

(2) Home Return (HOME, HEND)

Input

Output

PIO signal

HOME

HEND

The HOME signal is intended for automatic home return.

When the HOME signal is turned ON, the command will be processed at the leading edge (ON

edge) of the signal and the actuator will perform home return operation automatically.

Once the home return is completed, the HEND (home return completion) signal will turn ON.

Set the home (enter “0”) in the current value register of the host controller (PLC) using the

current value preset function, etc., when the HOME signal turns ON.

Caution:

(1) The HOME signal is given priority over any pulse train command. Even when the

actuator is moving with a pulse train command, it will start home return once the

HOME signal is turned ON.

(2) The HOME signal is processed only at the leading edge (ON edge) of the signal.

(3) If the SON signal is turned OFF or an alarm is detected during home return, the home

return operation will stop. If the servo is turned OFF, the home return command will be

cancelled even when the HOME signal remains ON. To perform home return again,

therefore, turn the HOME signal OFF and then turn it ON again.

(4) The actuator can be operated without using this function. If this function is not used,

however, management of position data will solely be dependent on the host controller

(monitoring soft stroke limit is effective in the home return complete status).

Therefore, take the necessary measures to prevent an over-stroke, such as not

sending pulse commands with travel distances exceeding the effective stroke or

providing external limit switches for stroke end detection, etc., to forcibly stop the

actuator.

(5) By turning the servo OFF or having the deviation counter cleared, HEND turns OFF.

Perform home return again.

[Operation of Actuator]

1) With the HOME signal being ON, the actuator moves toward the mechanical end at the

home return speed.

The movement speed is 20mm/s.

2) The actuator is turned at the mechanical end and stopped at the home position. The

moving distance is the value set by Parameter No.22 “Home return offset level”.

Caution: In the home reverse specification, the actuator moves in the reverse direction.

Make sure to refer to 6.3.1 [2] (15) when a change to Parameter No.22 “Home

return offset level” is required.

Mechanical end

Home

1)

2)