1] noise elimination grounding (frame ground) – IAI America ERC3 User Manual
Page 96
Chapter 2 Installation
2.3 How to Install
86
2.3.4 Noise Prevention and How to Attach Electrical Devices
[1] Noise Elimination Grounding (Frame Ground)
(1) When controlling ERC3 directly from the host controller (PLC)
Cable model code: CB-ERC3P-PWBIOƑƑƑ
ERC3 possesses a built-in controller in the actuator body. The frame ground line for this
controller is equipped in the PIO type power and I/O cable. Connect this to the ground terminal
using a relay terminal block.
For the grounding line after the relay terminal apply a low carbon steel wire with the diameter
1.6mm (AWG14: 2mm
2
) or more.
PLC
Earth Terminal
Class D grounding
(Formerly Class-III grounding :
Grounding resistance at 100: or less)
Do not share the ground wire with or connect
to other equipment. Ground each controller.
ERC3
Other
equipment
ERC3
Other
equipment
Other
equipment