1] noise elimination grounding (frame ground) – IAI America ERC3 User Manual

Page 96

Advertising
background image

Chapter 2 Installation

2.3 How to Install

86

2.3.4 Noise Prevention and How to Attach Electrical Devices

[1] Noise Elimination Grounding (Frame Ground)

(1) When controlling ERC3 directly from the host controller (PLC)

Cable model code: CB-ERC3P-PWBIOƑƑƑ

ERC3 possesses a built-in controller in the actuator body. The frame ground line for this

controller is equipped in the PIO type power and I/O cable. Connect this to the ground terminal

using a relay terminal block.

For the grounding line after the relay terminal apply a low carbon steel wire with the diameter

1.6mm (AWG14: 2mm

2

) or more.

PLC

Earth Terminal

Class D grounding

(Formerly Class-III grounding :

Grounding resistance at 100: or less)

Do not share the ground wire with or connect

to other equipment. Ground each controller.

ERC3

Other

equipment

ERC3

Other

equipment

Other

equipment