3 circuit diagram, 1] power line and emergency stop circuit, Sample circuit diagrams are shown below – IAI America ERC3 User Manual

Page 137

Advertising
background image

Chapter 3 Wiring

3.4 MEC Mode 1 (Operation with PLC)

127

3.4.3 Circuit Diagram

Sample circuit diagrams are shown below.

[1] Power Line and Emergency Stop Circuit



+

24V

0V

External

emergency

stop

reset switch

External

emergency

stop switch

Emergency-stop switch

on the teaching pendant

CR

CR

Connection

detection circuit

(Note 3)

Driving power

interrupting circuit

CR

(Note 1)

CR

ERC3

EMG

MP

CP

BK

Motor

power

supply

Control power supply

OR 1

OR

BR

RD 1

Brake release

switch

(Note 2)

Brake forcible release

MP_GND

B4

CP_GND

B2

YW

RD

CR

(Note 1)

CR

ERC3 2nd unit

OR 1

OR

BR

RD 1

EMG

MP

BK

CP

MP_GND

CP_GND

YW

RD

CR

(Note 1)

CR

ERC3 3th unit or later

OR 1

OR

BR

RD 1

EMG

MP

BK

CP

MP_GND

CP_GND

YW

RD

B4

B2

B4

B2

A4

B3

B1

A3

A4
B3
B1
A3

A4
B3
B1
A3





Note 1 The load current for the emergency stop signal to turn ON/OFF at contact CR is 24V DC and

10mA.

Note 2 This is a switch to compulsorily release the brake of the actuator equipped with a brake. It is

convenient when in maintenance or adjustment work if it is installed. It is necessary to have at

least 24V DC and 150mA for the switch contact capacity.

Note 3 The controller automatically identifies that the teaching tool is connected and activates the

emergency stop switch of the teaching pendant.

Caution:

• Do not attempt to shut the 0V circuit of MP_GND and CP_GND with the emergency stop. Doing

so may burn the internal circuit. If an absolute shutoff of the power supply is required, conduct it

on the primary side of DC power supply (alternating current side).

• The emergency stop switch of the teaching pendant cannot be reflected to the emergency stop

circuit of the whole system.

• In case the power source for each controller is different, join the 0V of each power supply

together.