Chapter 6

Adjustment of Operation

6.3 I/O Parameter

6.3.1 Positioner Mode 1, Positioner Mode 2 and Pulse

Train Control Mode

316

[For Positioner Mode 2]

Type

Value set in

parameter

No.25

Mode

Overview

PIO

Pattern 0

0

(at the

delivery)

Positioning mode

(Standard type)

x

Number of positioning points : 64 points

x

Position command : binary code

x

Zone signal output

*1

: 1 point

x

Position zone signal output

*2

: 1 point

(Note 1)

PIO

Pattern 1

1

Teaching mode

(Teaching type)

x

Number of positioning points : 64 points

x

Position command : binary code

x

Position zone signal output

*2

: 1 point

(Note 1)

x

Writing current position data to position table

enabled by PIO signal

PIO

Pattern 2

2

256-point mode

(Number of positioning

points : 256-point type)

x

Number of positioning points : 256 points

x

Position command : binary code

x

Position zone signal output

*2

: 1 point

(Note 1)

PIO

Pattern 3

3

512-point mode

(Number of positioning

points : 512-point type)

x

Number of positioning points : 512 points

x

Position command : binary code

x

Zone signal output : None

PIO

Pattern 4

4

Solenoid valve mode 1

(7-point type)

x

Number of positioning points : 7 points

x

Position command : Individual number signal ON

x

Zone signal output

*1

: 1 point

x

Position zone signal output

*2

: 1 point

(Note 1)

PIO

Pattern 5

5

Solenoid valve mode 2

(3-point type)

x

Number of positioning points : 3 points

x

Position command : Individual number signal ON

x

Completion signal : Signal equivalent to LS

(limit switch) enabled

x

Zone signal output

*1

: 1 point

x

Position zone signal output

*2

: 1 point

(Note 1)

*1 Zone signal output



Zone range is to be set to either Parameter No.1, 2 or No.23,

24

(Note 1)

and it is always available after the home-return

operation is complete.

*2 Position zone signal output : This feature is associated with the specified position number.

The zone range is set in the position table. The zone range is

enabled only when the position is specified but disabled if

another position is specified.

Note 1 The position zone signal output can be switched over to the zone signal output with

the setting of Parameter No.149.

(18) PIO jog velocity (Parameter No.26), PIO jog velocity 2 (Parameter No.47)

No.

Name

Symbol

Unit

Input Range

Default factory setting

26 PIO jog velocity

IOJV

mm/s 1 to Actuator’s max.

speed

100

47 PIO jog velocity 2

IOV2

mm/s 1 to Actuator’s max.

speed

100

This is the setting of JOG operation speed by PIO signal when PIO Pattern 1 is selected in

Positioner Mode 2.

Set the appropriate value considering how the system is to be used.

The maximum speed is limited to 250mm/s.

Note 1 Parameter No.47 “PIO jog velocity 2” is not used.