IAI America ERC3 User Manual

Page 369

Advertising
background image

Chapter 7

Troubleshooting

7.2 Fault Diagnosis

359

[In the case of Pulse Train Control Mode]

Situation

Possible cause

Check/Treatment

The actuator does not

stop at the command

position.

PIO signal processing or parameter

setting is incorrect.

1) Incorrect electronic gear ratio

2) Acceleration/deceleration is set

incorrectly in the host controller.

3) Noise

4) The pulse-train type, a parameter, is

selected incorrectly.

5) The unit moving distance per pulse,

which is a setting condition of

electronic gear ratio, a parameter, is

too small.

1) Check the setting of electronic gear

ratio. The host controller also has

the electronic gear ratio parameter.

Set the electronic gear ratio not to

be inconsistent with that of the host

controller. In addition, reduce the

electronic gear ratio as much as

possible. If not, data overflow may

occur in arithmetic processing to

disable correct positioning.

[Refer to Chapter 4, 4.3 [3] (1)

Electrical Gear Setting.]

2) The actuator operates at the speed

and acceleration/deceleration

based on the frequency of input

pulses. Check if the

acceleration/deceleration set in the

host controller exceed the rating

acceleration/deceleration of the

actuator.

3) Noise can be misread as the pulse

if it jumps into the pulse train.

Take proper measures against

noise. [Refer to Chapter 2, 2.3.4

Noise Prevention and How to

Attach Electrical Devices.]

Check the cable connection

between the controller and AK-04 if

AK-04 is used.

• Cable length :

50mm or shorter recommended

(as short as possible)

• Shield treatment :

Use the shield treatment wire.

4) Check the pulse-train type.

[Refer to Chapter 4, 4.3 [3] (2)

Format Settings of Command

Pulse Train.]

5) Do not make the unit moving

distance less than the resolution of

the encoder. The actuator does not

move unless pulses by the

resolution of the encoder are input.

[Refer to Caution in Chapter 4, 4.3

[3] (1) Electronic Gear Setting]

(Note) In case of 2) or 3), the

actuator may not sometimes

operate.

You may not find case 4)

when the actuator is moved

for a long distance at a high

frequency.

The actuator does not

reach the command

position when operated

with extremely low

speed.

To avoid unnatural move, the actuator

would not move unless the differential

pulse becomes 3 pulses or more.

Set to the full-servo mode.

(Set Parameter No.53 Stop Mode initial

setting to 4.)

Advertising