Chapter 4 Operation

4.2 Operation in Positioner Mode

4.2.2 Operation in Positioner Mode 1

180

Judging completion of pressing operation

The operation monitors the torque (current limit value) in percent in “Pressing” of the position

table and turns pressing complete signal PEND ON when the load current satisfies the

condition shown below during pressing. PEND is turned ON at satisfaction of the condition if

the work is not stopped.

(Accumulated time in which current reaches pressing value [%]) – (accumulated time in

which current is less than pressing value [%]) t 255ms (Parameter No.6)



Current

Time

Pressing [%]

Operation

start

Approach end

Pressing start

200ms

20ms

75ms

295ms

200ms + 75ms - 20ms • 255ms

Pressing Completion (PEND Output)

Contacting work

Decrease in current due to movement of work