Wiring, Exchange connection – Toa N-8000 Series User Manual

Page 357

Advertising
background image

3-53

Chapter 3

INSTALLATION & WIRING

13. WIRING

13.1. exchange Connection

N-8000EX/8010EX Exchange

To AC mains or a UPS

(Uninterruptible power supply system)*

16 lines

Note

Be sure to ground.

Both upper and lower terminals (clip terminals)

are internally connected.

Mini-clamp connector

232D-02S1B-DA5 (DDK)

(Supplied with the N-8000EX/8010EX)

Lines should be twisted

E-7000TB

Terminal board

Station

If there is a danger of lightning strikes,

insert an appropriate power gap arrester

into the power line.

* Select an appropriate UPS taking into consideration the total power consumption of all system components

and the required backup time. On-line uninterruptible power supply (UPS) is recommended.
Reference

Exchange: 50 W (rated)

8-Port 10M/100M Switching Hub: 10 W (Differs depending on products.)

Note

Once the station line connected between a station and the

exchange is short-circuited or a ground fault occurs on the

cable, power cannot be supplied to the station even when

the short or ground fault is removed.

To restore the situation, be sure to disconnect the cable

connector at the station or exchange, and then connect it

again after several seconds.