P. 5-108 – Toa N-8000 Series User Manual

Page 518

Advertising
background image

Chapter 5

SYSTEM SETTINGS BY SOFTWARE

Audio Interface: Function Settings

5-108

(2) External timer

Perform settings for broadcasting time signals enabled by a make signal from external equipment connected

to the contact input of the audio interface unit.

Contact Input:

The Audio interface unit’s contact input terminal number. (Can’t be edited.)

Enable:

Enables the external timer function of the selected contact input.

Source:

Set the sound source number to be activated when the selected contact input

terminal is closed. Numbers 1 – 5 correspond to internal sound sources,

while numbers 6 – 9 correspond to external sound sources (contact outputs

1 – 4).

Access to external control: Controls the contact output terminal set in the External Equipment Activation

setting when the selected contact input terminal is closed.

Paging No.:

Set the paging zone over which broadcasts are made when the selected

contact input terminal is closed.

(3) External control

External equipment can be set to be activated when the timer-controlled or time signal programs are

initiated.

Equipment No.:

Select the equipment number of the Multi interface unit, Direct select unit,

or Audio interface unit of which operation mode is set to "Time signal."

Contact No.:

Select one of the contact output terminals. When the target unit is Audio

interface unit, only the terminal numbers 5 to 8 can be set.

Activation time:

Set the time interval that activates the contact (1 – 1,024 sec).

(4) Schedule

Up to 16 types of schedules can be registered, and up to 64 events registered for each schedule.

Enable Schedule No.:

Activated schedule number: Set the schedule number to be used.

Each schedule settings:

Selecting one of tabs 1 – 16 allows each schedule to be set.

New button:

Add new events. Up to 64 events can be added per individual schedule.

Clicking the "New" button displays the New Event screen.

Step 3-1. Set the New event.

(1) Name

Set an event name.

The name is displayed on the multi-function master station's LCD screen. The name must be of 8 characters

or less.

(2) Time

Set the time that the event takes place.

Advertising