Trial Operation

5.2.5 Autotuning

- 6

4. Replace the front cover.

400/415V

21CN

380V

440V

460V

23CN 24CN 25CN 26CN 22CN FU2

20CN

TB2

r

Jumper

Fig

5.1

Setting the Power Supply Voltage (Illustration Above is for 400 V Class Inverter
between 18.5 kW and 45 kW)

J

Motor Selection (Motor Overheating Protection): E1-02

Set the type of motor being used with the motor selection constant (E1-02). This setting is a reference for
the motor overheat protection.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

E1-02

Motor selection

(motor overheating
protection)

0 to 2

--

0

Q

Q

D

E1-02 Settings

Setting

Function

0

Standard motor (general-purpose motor)

1

Special motor (inverter-exclusive motor)

2

Special motor (vector-exclusive motor)

5.2.5 Autotuning

J

Autotuning Operation

Use the following procedure to autotune the motor constants, i.e., set them automatically.

Step

Key Sequence

Digital Operator Display

Remarks

MC5

Main Menu

Programming

Displays programming mode.

1

MC5

Main Menu

Auto--Tuning

Displays autotuning mode.

2

DATA

ENTER

Rated Voltage

*

1

200. 0 VAC

Displays the rated voltage.

*2

3

Rated Current

*

1

1. 90 A

Displays the rated current.

*2

4

Rated Frequency

*

1

60. 0 HZ

Displays the rated frequency.

*2

5

Rated Speed

*

1

1750 RPM

Displays the rated speed.

*2

6

Number of Poles

*

1

4

Displays the number of poles.

*2

7

Select Motor 1/2

1

Displays the motor selection.
(Leave set at “1” for motor 1 (the nor-
mally used motor constants).)

8

Tuning Ready ?

Press RUN key

Displays a confirmation prompt for
the start of the autotuning function.
(The lower line will blink.)

9

RUN

Tune Proceeding

HZ

A

Starts the autotuning function.
(The upper line will blink.)

5