Yaskawa VS-626 MC5 User Manual

Page 101

Advertising
background image

5.2

Trial Operation Procedures

- 7

Step

Key Sequence

Digital Operator Display

Remarks

Tune Successful

Indicates the completion of autotun-
ing.

10

MENU

MC5

Main Menu

Operation

Returns to the operation mode dis-
play.

* 1. When the values displayed and the motor rated values differ, set each value separately.
* 2. There are differences between simple and advanced settings. Refer to the table below.

Operator Display

Simple Setting

(Motor nameplate)

Advanced Setting

Rated Voltage

Motor rated voltage

No--load voltage at rated revolu-
tions

Rated Frequency

Motor rated frequency

No--load frequency at rated revolu-
tions

Rated voltage for vector control motors is approx. 10 to 20% lower than general--purpose motors.
Always verify motor voltage listed on the nameplate or test report before use.
The following example procedure changes the motor rated current to 1.60 A.

Step

Key Sequence

Digital Operator Display

Remarks

Rated Current

1. 90 A

Displays the rated current.

1

DATA

ENTER

Rated Current

001. 90 A

When changing the set values, press
the DATA/ENTER Key and the digit
to change will blink.

2

Press 3 times

RESET

Rated Current

001. 90 A

Select the digit to be changed.

3

Press 3 times

Rated Current

001. 60 A

Set to 001.60 A.

4

DATA

ENTER

Entry Accepted

Press the DATA/ENTER Key to over-
write the set values. “Entry Accepted”
will be displayed for approximately
0.5 seconds.

Rated Current

1. 60 A

Returns to the rated current display.

D

When autotuning has been executed correctly, the constants (E1-04 to E2-09) will be automatically
written.

D

Use the following troubleshooting procedure is a fault occurs during autotuning.

J

Troubleshooting Autotuning Faults

The displays and countermeasures for autotuning faults are shown below in Table 5.1. If one of these faults
is detected, it will be displayed on the Operator and the motor will coast to a stop. The fault contact and
alarm contact outputs will not function. When a fault occurs, “Tune Aborted” will be displayed and the
messages shown in the following table will blink.

Table

5.1

Troubleshooting Autotuning Faults

Display Message

Fault

Description

Countermeasure

Data Invalid

Motor data fault

Motor data error for autotuning.

S Check the input data.
S Check the Inverter and motor capacities.

Resistance

Line resistance fault

No-load Current

No-load current fault

Saturation -1

Saturated core coeffi-
cient 1 fault

Autotuning was not completed
within a set time.

S Check the input data.
S Check the motor wiring

Saturation -2

Saturated core coeffi-
cient 2 fault

within a set time.

S Check the motor wiring.

Rated Slip

Rated slip fault

Accelerate

Acceleration fault

The motor did not accelerate with-
in a set time.

S Increase the acceleration time (C1-01).
S Increase the torque limits (L7-01, -02) if

these have been decreased.

S Disconnect the motor from the machine if

it has been connected.

5