1 standard inverter specifications – Yaskawa VS-626 MC5 User Manual

Page 263

Advertising
background image

Specifications

- 2

11.1 Standard Inverter Specifications

Table

11.1

200 V Class Inverters

Model number
CIMR-MC5A

20P4

20P7

21P5

22P2

23P7

25P5

27P5

2011

2015

2018

2022

2030

2037

2045

2055

2075

Max. applicable motor
output (kW)

0.4

0.75

1.5

2.2

3.7

5.5

7.5

11

15

18.5

22

30

37

45

55

75

Rated output capac-
ity (kVA)

1.2

2.3

3.0

4.2

6.7

9.5

13

19

24

30

37

50

61

70

85

110

Ou

Rated output current
(A)

3.2

6

8

11

17.5

25

33

49

64

80

96

130

160

183

224

300

Ou

Max. output voltage
(V)

3-phase, 200 to 230 VAC (Proportional to input voltage.)

Rated output fre-
quency (Hz)

Up to 400 Hz (available by programming)

Voltage (V)
Frequency (Hz)

3-phase, 200 to 230 VAC, 50/60 Hz

Po

Allowable voltage
fluctuation

+10%, --15%

Allowable frequency
fluctuation

5%

Control method

Sine wave PWM

Torque characteris-
tics

150% at 1 Hz (150% at 0 r/min with PG).

2

Speed control range

1: 100 (1: 1000 with PG)

*2

Speed control accu-
racy

0.2% (

r0.02% with PG)

*2

Speed control re-
sponse

5 Hz (30 Hz with PG)

*2

Torque limits

Provided (4 quadrant steps can be changed by Ccnstant settings.)

Torque accuracy

5%

Frequency control
range

0.1 to 400 Hz

Frequency accuracy
(temperature charac-

Digital references:

0.01% (--10 to +40 )

(temperature charac-
teristics)

Analog references: 0.1% (25

10 )

Co

Frequency setting

Digital references: 0.01 Hz

Co

Frequency setting
resolution

Analog references: 0.03 Hz/60 Hz (11 bits + sign)

Output frequency
resolution

0.001 Hz

Overload capacity

150% of rated current for one minute

Frequency setting
signal

--10 to 10 V, 0 to 10 V, 4 to 20 mA

Acceleration/Decel-
eration time

0.01 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)

Braking torque

Approximately 20%

Motor protection

Protection by electronic thermal overload relay.

Instantaneous over-
current protection

Stops at approx. 200% of rated output current.

Fuse blown protec-
tion

Stops for fuse blown.

Overload protection

Stops in one minute at approx. 150% of rated output current.

Overvoltage protec-
tion

Stops when main-circuit DC voltage is approx. 410 V.

Pr

Undervoltage protec-
tion

Stops when main-circuit DC voltage is approx. 190 V.

Momentary power
loss ridethru

Stops for 15 ms or more. By selecting the momentary power loss mode, operation can be continued if power is restored within 2 s.

Cooling fin overheat-
ing

Protection by thermistor.

Stall prevention

Stall prevention during acceleration, deceleration, or running.

Grounding protection

Protection by electronic circuits. (Overcurrent level)

Charge indicator (in-
ternal LED)

Lit when the main circuit DC voltage is approx. 50 V or more.

11