Advanced Operation

7.3.6 Protective Functions: L

- 52

Output current

Time

L3-02 (Acceleration stall prevention level)

Output frequency

Time

The output frequency is controlled to prevent stalling.

Fig

7.30

Acceleration Stall Prevention Function: L3-01 = 1

Stall Prevention Limit During Acceleration: L3-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L3-03

Stall prevention limit
during accel

0 to 100

%

50

A

D

Normally it isn’t necessary to change this setting.

D

Set this constant when a high-speed motor is being used in the high-speed range (the high frequency
range above the base frequency).

D

The standard target setting is the motor’s rated current. Set this current value as a percentage of the
Inverter’s rated current, i.e., 100% corresponds to the Inverter’s rated current.

E1-06

Base frequency (F

A

)

Acceleration stall
prevention level

L3-02
(Acceleration stall preven-
tion level)

L3-03
(Acceleration stall prevention
limit)

Output frequency

Note When the motor is used in the high-speed range, the acceleration stall prevention level

is automatically lowered to provide smoother acceleration.
The acceleration stall prevention limit (L3-03) limits how much the acceleration stall
prevention level is lowered so that it isn’t lowered any more than necessary.

Fig

7.31

Stall Prevention Limit During Acceleration