Yaskawa VS-626 MC5 User Manual

Page 112

Advertising
background image

6.1

Common Settings

- 9

6.1.4 Run Source and Sequence Input Responsiveness: b1-02, b1-06, b1-07

J

Run Source: b1-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

b1-02

Operation method selec-
tion

0 to 5

--

1

Q

Q

D

Constant b1-02 is used to select the source of the run command.

D

When a control circuit terminal (external terminal) is set, the Unit operates with 2-wire forward run/
stop and reverse run/stop control. (When the Unit has been initialized for a 3-wire control or a multi-
function input is set to 0 (3-wire sequence), the Unit operates with 3-wire run, stop and forward/reverse
controls.)

D

When using winding change function, set b1-02 to “5” (winding change sequence).

D

Settings

Setting

Run source

0

Digital Operator

1

Control circuit terminals (external terminals)

2

Transmission

3

Optional Card

4

MEMOBUS transmission (for CP--717)

5

Winding change sequence

J

Sequence Input Responsiveness (Reading Twice): b1-06

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

b1-06

Read sequence input
twice

0 1

--

1

A

A

D

Set the responsiveness of the control inputs (forward/reverse run and multi-function inputs)

D

Settings

Setting

Function

0

Two scans every 2 ms (Use when connecting transistor outputs.)

1

Two scans every 5 ms (Use when connecting contact outputs or switches.)

D

Set the responsiveness to match the type of control inputs being used. Use a setting of 1 if there is one
or more contact inputs.

J

Operation after Switching to Remote Mode: b1-07

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

b1-07

Operation selection after
switching to remote
mode

0 1

--

0

A

A

D

Set the interlock operation to be used after switching from local mode (operation from Digital Opera-
tor) to remote mode (operation according to control circuit terminal).

D

Settings

Setting

Function

0

No operation even if RUN signal is ON after switching to remote mode. (Operation will start if
the RUN signal turns OFF and then back ON after switching to remote mode.)

1

Operate according to the RUN signal after switching to remote mode.

6