Advanced Operation

7.4.2 Wiring for Winding Change

- 66

Minimum Baseblock Time: L2-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L2-03

Min. baseblock time

0.0 to 5.0

s

0.5

B

B

D

The factory setting depends on the Inverter capacity. The factory setting shown in the table is for a

200 V class, 0.4 kW Inverter. (See page NO TAG.)

D

This setting is used with the speed search and DC injection braking functions.

D

Set the time required for the leakage voltage to dissipate. Increase the setting if an overcurrent (OC)
occurs when the speed search or DC injection braking function starts.

D

Set the baseblock time during winding change. Time for winding change varies according to the set-
ting. (For example, lower the setting, and time for winding change is also reduced.) Overcurrent (OC)
might occur if setting is too low.

D

This setting is valid for speed searches performed after a momentary power loss and regular speed
searches.

Voltage Recovery Time: L2-04

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L2-04

Voltage recovery time

0.0 to 5.0

s

0.3

A

A

D

Set the time allowed for the normal voltage to be restored after completion of the speed search.
For a 200 V class Inverter, this is the time in seconds for voltage to be restored from 0 VAC to 200 VAC.
For a 400 V class Inverter, this is the time in seconds for voltage to be restored from 0 VAC to 400 VAC.

D

This setting is valid for speed searches after a momentary power loss, regular speed searches, the volt-
age changes with energy-saving control, and the voltage changes with baseblock clearing.

D

Set the voltage recovery time after baseblock during winding change. Ovrevoltage (OV) might occur
if setting is too low.

Speed Search Deceleration Time: b3-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

b3-03

Speed search decelera-
tion time

0.1

10.0

s

2.0

A

D

Set output frequency deceleration time during speed search. (Set the time to decelerate from the max.
output frequency to OHz.)

7.4.2 Wiring for Winding Change

The VS-626MC5 offers two different types of winding changes, external winding change and auto- wind-
ing change. W-winding and -winding can be set independently using constants for motor 1 and 2.

J

External Winding Change Method

In this method, an external signal is given to one of the multi-function inputs (set as “80H”) to start the
winding change. The external signal is given from the CNC.

MC Answerback error detection

:

P1-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

P1-03

MC Answerback error
detection

0.20 to 1.00

sec

0.20

A

A

D

This constant determines the waiting time for the MC (Magnetic Contactor) answerback error detec-
tion.

D

Setting is valid when one of the multi-function digital inputs (H1-01 to H1-06) has been set to 81 or
82.

Motor constant selection: P1-04

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

P1-04

Motor constant selection

0 1

--

1

A

A

D

Select the motor constants allocated for the types of winding to be used.

7