background image

2.4

Installation Orientation and Space

- 7

2.4

Installation Orientation and Space

Install the Inverter on a vertical surface so as not to reduce the cooling effect. When installing the Inverter, al-
ways provide the following installation space to allow normal heat dissipation.

(

a

) Horizontal Space

50 mm min.

30 mm min. 30 mm min.

50 mm min.

(

b

) Vertical Space

120 mm min.

120 mm min.

Air

Air

Fig

2.1

VS-626MC5 Installation Orientation and Space

S The same space is required horizontally and vertically for both open chassis (IP00) and enclosed

wall-mounted (IP20, NEMA 1) Inverters.

S Always remove the protection covers before installing a 200 or 400 V Class Inverter with an output

of 15 kW or less in a panel.

S Always provide enough space for suspension eye bolts and the main circuit lines when installing a

200 or 400 V Class Inverter with an output of 30 kW or more in a panel.

2

IMPORTANT