Basic Operation

6.1.5 Acceleration/Deceleration Times: C1-01 through C1-08, C1-09, C1-10, C1-11

- 10

6.1.5 Acceleration/Deceleration Times: C1-01 through C1-08, C1-09, C1-10, C1-11

This section describes setting the acceleration times, deceleration times, and emergency stop time.

J

Acceleration/Deceleration Time Unit: C1-10

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

C1-10

Accel/decel time setting
unit

0 1

--

1

A

A

D

Settings

Setting

Function

0

Sets the acceleration/deceleration time unit to 0.01 seconds.

1

Sets the acceleration/deceleration time unit to 0.1 seconds.

D

Set “0” to set more precise acceleration and deceleration times. (This will reduce the setting range.)

J

Acceleration/Deceleration Times: C1-01 through C1-08

D

Set individual acceleration and deceleration times.

x

An acceleration time is the time required to go from 0% to 100% of the maximum output frequen-
cy.

x

A deceleration time is the time required to go from 100% to 0% of the maximum output frequency.

D

Four acceleration times and four deceleration times can be set. When using acceleration/deceleration
times 2 through 4, set multi-function inputs (H1-01 through H1-06) to the acceleration/deceleration
time selectors 1 and 2.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

C1-01

Acceleration time 1

0.0 to

6000.0

s

10.0

Q

Q

C1-02

Deceleration time 1

0.0 to

6000.0

s

10.0

Q

Q

C1-03

Acceleration time 2

0.0 to

6000.0

s

10.0

B

B

C1-04

Deceleration time 2

0.0 to

6000.0

s

10.0

B

B

C1-05

Acceleration time 3

0.0 to

6000.0

s

10.0

A

A

C1-06

Deceleration time 3

0.0 to

6000.0

s

10.0

A

A

C1-07

Acceleration time 4

0.0 to

6000.0

s

10.0

A

A

C1-08

Deceleration time 4

0.0 to

6000.0

s

10.0

A

A

D

The setting range for the acceleration/deceleration times depends on the setting in C1-10 (acceleration/
deceleration time unit). The table shows the setting range when the factory setting is used for C1-10.

D

If C1-10 is set to “0” (0.01 s) the setting range will be 0.00 to 600.00 s.

J

Emergency Stop Time: C1-09

D

Sets the deceleration time that will be used when an emergency stop signal is input or a fault is detected.
The deceleration time is the time required to go from 100% to 0% of the maximum output frequency.

D

When using an emergency stop input, set a multi-function input (H1-01 through H1-06) to for an emer-
gency stop.

D

The emergency stop time is effective for the following faults. Set a stopping method for each.

x

Inverter overheating (OH) pre-alarm: Set in L8-03.

x

Pulse generator faults: Set in F1-02 through F1-04.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

C1-09

Emergency stop time

0.0 to

6000.0

s

10.0

B

B

6