Yaskawa VS-626 MC5 User Manual

Page 76

Advertising
background image

4.2Modes

- 13

Func-

tion

Valid Access Levels

Min.

Unit

Output Signal Levels for

Multi-function Analog Out-

puts

Function

Name

Con-
stant

No.

Func-

tion

Flux

Vector

Open Loop

Vector

Min.

Unit

Output Signal Levels for

Multi-function Analog Out-

puts

Function

Digital Operator

Display

Con-
stant

No.

U1-12

Operation status

Inverter operating status.

U1-12 = 0 0 0 0 0 0 0 0

1: Running

1: Zero-speed level

1: Reverse

Can’t be output

Q

Q

U1-12

Int Ctl Sts 1

1: Reverse

1: Reset input ON

1: F.ref/F.out agree

1: Inverter ready

1: Minor fault detected

1: Major fault detected

Can’t be output.

Q

Q

U1-13

Cumulative opera-
tion time

Monitors the Inverter’s elapsed
operating time.
The initial value and running/
power on time selection can be

Can’t be output.

1 hr

Q

Q

U1 13

Elapsed Time

g

power-on time selection can be
set with user constants o2-07
and o2-08.

Can t be output.

1 hr

Q

Q

U1-14

Software No.

Manufacturer’s ID number

Can’t be output

Q

Q

U1-14

FLASH ID

Manufacturer’s ID number

Can’t be output.

Q

Q

U1-15

Terminal 13 input
voltage level

Monitors the input voltage of
the frequency reference (volt-
age).

10 V: 100% (10 V)
(0 to

r10 V possible)

0.1 %

B

B

U1 15

Term 13 Level

age).
An input of 10 V corresponds to
100%.

(0 to

r10 V possible)

0.1 %

B

B

U1-16

Terminal 14 input
current level

Monitors the input current of the
frequency reference (current).
An inp t of 20 mA corr sponds

20 mA: 100% (20 mA)
(0 to +10 V output)

0.1 %

B

B

U1 16

Term 14 Level

An input of 20 mA corresponds
to 100%.

(0 to +10 V output)

0.1 %

B

B

Status
Moni-
tor

U1-17

Terminal 16 input
voltage level

Monitors the input voltage of
the multi-function analog input.
An inp t of 10 V corr sponds to

10 V: 100% (10 V)
(0 to

r10 V possible)

0.1 %

B

B

tor

U1 17

Term 16 Level

An input of 10 V corresponds to
100%.

(0 to

r10 V possible)

0.1 %

B

B

U1-18

Motor secondary
current (lq)

Monitors the calculated value of
the motor’s secondary current
(Iq).

10 V: Rated secondary cur-
rent

0.1 %

B

B

U1 18

Mot SEC Current

(Iq).
The motor’s rated secondary
current corresponds to 100%.

e t

(0 to +10 V output)

0.1 %

B

B

U1-19

Motor exciting cur-
rent (ld)

Monitors the calculated value of
the motor’s excitation current
(Id).

10 V: Rated secondary cur-
rent

0.1 %

B

B

U1 19

Mot EXC Current

(Id).
The motor’s rated secondary
current corresponds to 100%.

e t

(0 to +10 V output)

0.1 %

B

B

U1-20

Output frequency
after soft-start

Monitors the output frequency
after a soft start.
The display shows the frequen-
cy without the correction from

10 V: Max. frequency
(0 to

r10 V possible)

0.01

Hz

A

A

U1 20

SFS Output

p y

q

cy without the correction from
compensation functions such as
slip compensation.

(0 to

r10 V possible)

Hz

A

A

U1-21

ASR input

Monitors the input to the speed
control loop.

10 V: Max. frequency

0 01 %

A

U1-21

ASR Input

co t o oop.
The max. frequency corresponds
to 100%.

10 V: Max. frequency
(0 to

r10 V possible)

0.01 %

A

U1-22

ASR output

Monitors the output from the
speed control loop.

10 V: Rated secondary cur-
rent

0 01 %

A

U1-22

ASR Output

speed co t o oop.
The motor’s rated secondary
current corresponds to 100%.

rent
(0 to

r10 V possible)

0.01 %

A

U1-23

Speed deviation

Monitors the speed deviation
within the speed control loop.

10 V: Max. frequency

0 01 %

A

U1-23

Speed Deviation

w t

t e speed co t o oop.

The max. frequency corresponds
to 100%.

10 V: Max. frequency
(0 to

r10 V possible)

0.01 %

A

4