3 using two braking units in parallel – Yaskawa VS-626 MC5 User Manual

Page 280

Advertising
background image

12.4

Wiring Examples

- 11

12.4.3 Using Two Braking Units in Parallel

5

+15

Braking Unit 2

MCCB

3-phase power
200 to 230 V
50/60 Hz

Motor

IM

M

r

Cooling fan

VS-626MC5

Braking Unit

3

4

3

(Ground to 100

:

max.)

Thermal protector

1

2

Braking
Resis-
tor Unit

P

1

2

3

4

Thermal switch

B

Thermal switch

6

P

Level

MASTER

SLAVE

Overload relay trip contact of
Braking Resistor Unit

A sequence is required to turn
OFF the power supply for the
thermal overload relay trip con-
tacts of the Braking Resistor Unit.

Disable stall prevention during deceleration by setting L3-04 to “0” or “3” when using a
Braking Resistor Unit. The motor may not stop within the deceleration time if this setting is
not changed.

5

Thermal protector

1

2

Braking
Resis-
tor Unit

P

1

2

3

4

B

6

MASTER

SLAVE

R

S

T

MC

U

V

W

R

S

T

©

¨

3

THRX

OFF

ON

MC

SA

1

2

MC

TRX

TRX

20 18

Fault contacts

SA

SA

THRX

MC

©

©

¨

¨

¨

0

¨

0

©

0

©

0

Forward Run/Stop

Forward run command
(forward run when closed)

Reverse Run/Stop

Reverse run command
(reverse run when closed)

External fault

18

19

20

External contact
output

12