8.2

Programming Mode Constants

- 21

Setting

value

Page

Control Methods

Function

Setting

value

Page

Flux vector

Open loop

Vector

Function

81

MC answerback (N.C.)

- 68

82

MC answerback (N.O.)

- 68

J

Multi-function Outputs: H2

Constant

Setting

Factory

Change

during

Control Methods

Constant

Number

Name

Display

Setting

Range

Factory

Setting

g

during

Opera-

tion

Open Loop

Vector

Flux Vector

Page

H2-01

Multi-function input
(terminal 9-10)

Terminal 9 Sel

0 to 37

0

B

B

- 42

H2-02

Multi-function input
(terminal 25-27)

Terminal 25 Sel

0 to 37

1

B

B

- 42

H2-03

Multi-function input
(terminal 26-27)

Terminal 26 Sel

0 to 37

2

B

B

- 42

Multi-function Output Functions

Setting

Control Methods

Setting

value

Function

Open loop

Vector

Flux vector

Page

0

During run ON: run command is ON or voltage is being output)

- 43

1

Zero-speed

- 43

2

Frequency agree 1: (Detection width L4-02)

- 54

3

Desired frequency agree 1 (ON: Output frequency =

rL4-01, detection width in L4-02)

- 54

4

Frequency (Four) detection 1 (ON: +L4-01

output frequency--L4-01, detection width in

L4-02)

- 54

5

Frequency (Four) detection 2
(ON: Output frequency

+L4-01 or output frequency%--L4-01, detection width in L4-02)

- 54

6

Inverter operation ready

READY: After initialization, no faults

7

During DC bus undervoltage (UV) detection

8

During baseblock (ON: during baseblock)

9

Frequency reference selection (ON: Frequency reference from Operator)

A

Run command selection (ON: Run command from Operator)

B

Overtorque detection 1 NO (NO contact: Overtorque detection at ON)

- 56

C

Loss of frequency reference (Effective when operation selection is “1” for L4-05 frequency
reference missing)

- 54

D

Braking resistor fault (ON: Resistor overheat or braking transistor fault)

E

Fault (ON: Faults other than CPF00, CPF01 have occurred.)

NO TAG

F

Not used. (Do not set.)

10

Minor fault (ON: Alarm displayed)

NO TAG

11

Fault reset command active

12

Not used. (Do not set.)

13

Frequency agree 2 (Detection width: L4-04)

- 54

14

Desired frequency agree 2 (ON: Output frequency = L4-03, detection width in L4-04)

- 54

15

Frequency detection 3 (ON: Output frequency

%--L4-03, detection width in L4-04)

- 54

16

Frequency detection 4 (ON: Output frequency

--L4-03, detection width in L4-04)

- 54

17

Overtorque detection 1 NC (NC Contact: Ttorque detection at OFF)

- 56

18

Overtorque detection 2 NO (NO Contact: Torque detection at ON)

- 56

19

Overtorque detection 2 NC (NC Contact: Torque detection at OFF)

- 56

1A

During reverse run (ON: During reverse run)

1B

During baseblock 2 (OFF: During baseblock)

1C

Motor selection (ON:During moter 1 selection)

1D

Regenerating (ON: Regenerating)

1E

Restart enabled (ON: Restart enabled)

- 56

1F

Motor overload (OL1) pre-alarm (ON: 90% or more of the detection level)

- 43

20

Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting)

- 43

30

During torque limit (current limit) (ON: During torque limit)

31

During speed limit. (ON: During speed limit)

- 43

37

During run 2 (ON: Frequency output, OFF: Base block, DC injection braking, initial excita-
tion, operation stop.)

- 43