4 wiring examples, 1 using a braking resistor unit, 2 using a braking unit and braking resistor unit – Yaskawa VS-626 MC5 User Manual

Page 277: Appendix

Advertising
background image

Appendix

12.4.1 Using a Braking Resistor Unit

- 8

12.4 Wiring Examples

12.4.1 Using a Braking Resistor Unit

CIMR-MC5A20P4 to -MC5A27P5 (200 V class Inverters of 0.4 to 7.5 kW)
CIMR-MC5A40P4 to -MC5A4015 (400 V class Inverters of 0.4 to 15 kW)

Short-circuit bar

¨

1

DC Reactor to
improve input
power factor
(Optional)

Braking Resistor overheating contacts
(Thermal overload relay trip contacts)

Braking Resistor Unit

*3

VS-626MC5

MCCB

3-phase power
200 to 230 V
50/60 Hz
or
380 to 460 V
50/60 Hz

R

M
C

R (L1)

S

S (L2)

T

T (L3)

*1

400/200 V

THR
X

OFF

ON

M
C

SA

Overload relay trip contact
of Braking Resistor Unit

1

2

MC

TRX

TRX

20 18

Fault contacts

A sequence is required to turn
OFF the power supply for the
thermal overload relay trip con-
tacts of the Braking Resistor Unit.

¨

2

B1

B2

SA

SA

THR
X

U (T1)

V (T2)

W (T3)

Motor

IM

(200 V class Inverters: Ground
to 100

:

max., 400 V class In-

verters: Ground to 10

:

max.)

1

2

B

P

MC

©

*2

* 1

A transformer is not required for 200 V class Inverters.

* 2

Remove the short-circuit bar (normally connected) from between terminals

¨

1 and

¨

2 when connecting a DC Reactor (Optional).

* 3

Disable stall prevention during deceleration by setting L3-04 to “0” or “3”
when using a Braking Resistor Unit. The motor may not stop within the de-
celeration time if this setting is not changed.

12.4.2 Using a Braking Unit and Braking Resistor Unit

CIMR-MC5A2011 -MC5A2015 (200 V class Inverters of 11 kW 15 kW)

U (T1)

©

V (T2)

W (T3)

MCCB

R

MC

R (L1)

S

S (L2)

T

T (L3)

THRX

OFF

ON

MC

SA

Overload relay trip contact
of Braking Resistor Unit

1

2

MC

TRX

TRX

20 18

Fault contacts

SA

SA

THRX

3

Braking Unit

3

4

Motor

IM

(Ground to 100

:

max.)

¨

1

DC Reactor to
improve input
power factor
(Optional)

Braking Unit
(Optional)

¨

2

¨

3

¨

¨

0

P

B

Braking Resistor Unit

*2

(Optional)

1

2

Braking Resistor overheating contacts
(Thermal protector trip contacts)

Level
detector

3-phase power
200 to 230 V
50/60 Hz

3

4

VS-626MC5

©

MC

A sequence is required to turn
OFF the power supply for the ther-
mal overload relay trip contacts of
the Braking Resistor Unit.

*1

* 1

Remove the short-circuit bar (normally connected) from between termi-

nals

¨

1 and

¨

2 when connecting a DC Reactor (Optional).

* 2

Disable stall prevention during deceleration by setting L3-04 to “0” or “3”
when using a Braking Resistor Unit. The motor may not stop within the de-
celeration time if this setting is not changed.

Short-circuit bar

©

0

Forward Run/Stop

Forward run command
(forward run when closed)

Reverse Run/Stop

Reverse run command
(reverse run when closed)

External fault