Advanced Operation

7.3.6 Protective Functions: L

- 58

Inverter Overheating (OH) Pre-alarm Settings: L8-02 L8-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L8-02

Overheat pre-alarm lev-
el

50 to 110

95

A

A

L8-03

Operation selection after
overheat pre-alarm

0 to 3

--

3

A

A

D

Constant L8-02 specifies the detection temperature in

qC for the Inverter overheat (OH) pre-alarm

function. An overheat pre-alarm occurs when the temperature of the cooling fins reaches this level.

D

Constant L8-03 specifies the processing that will be performed when an overheat pre-alarm occurs.
Apart from this setting, cooling fin overheating (OH1) is detected as a protection function at 105_C.

D

Settings

Setting

Function

0

Decelerates to a stop in the deceleration time set in C1-09. (Protection operation: Fault contacts
operate)

1

Coast to stop. (Protection operation: Fault contacts operate)

2

Emergency stop in the emergency-stop time set in C1-09. (Protection operation: Fault contacts
operate)

3

Continues operation. (Alarm: Monitor display only.)

Input Open-phase Protection Selection: L8-05

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L8-05

Input open-phase
protection selection

0 1

--

0

A

A

D

This function detects changes in the main circuit DC voltage which indicate a power supply open-
phase, large imbalance in the power supply voltage, or deterioration of the main circuit capacitor.

D

Settings

Setting

Function

0

Disabled.

1

Enabled. (Detects input power supply open-phase, 3-phase imbalance, or deterioration of the
main circuit capacitor.)

Output Open-phase Protection Selection: L8-07

D

This function detects an Inverter output open-phase.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

L8-07

Output open-phase
protection selection

0 1

--

0

A

A

D

Settings

Setting

Function

0

Disabled.

1

Enabled. (Detects an output open-phase at under 10% of the Inverter’s rated output current.)

D

False open-phase detections may occur when the motor capacity is small compared to the Inverter ca-
pacity. In this case, disable the detection function by setting L8-07 to 0.

7