Yaskawa VS-626 MC5 User Manual

Page 143

Advertising
background image

7.1

Open-loop Vector Control

- 5

7.1.2 Adjusting Speed Feedback

With open-loop vector control, internal Inverter data is used to calculate the feedback value. The gain of
this automatic frequency regulator (AFR) operation can be fine-tuned according to motor response. (Nor-
mally it isn’t necessary to change the default setting.)

J

Speed Feedback Detection Control (AFR) Gain: C8-08

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

C8-08

AFR gain

0.00 to

10.00

Mul-

tiple

1.00

A

D

Normally it isn’t necessary to change this setting.

D

Fine-tune the gain when motor operation is unstable causing hunting to occur or torque/speed respon-
siveness is low.

x

When hunting occurs, increase the gain by 0.05 increments while checking the motor responsive-
ness.

x

When responsiveness is low, decrease the gain by 0.05 increments while checking the motor re-
sponsiveness.

7.1.3 Setting/Adjusting Motor Constants

J

Adjusting the V/f Pattern: E1-04 through E1-10, E1-13

Normally it isn’t necessary to adjust the V/f pattern with open-loop vector control. Adjust the V/f pattern
when you want to change the maximum output frequency setting or decrease the Inverter’s output voltage
or when stalls are occurring during no-load operation.
To increase the motor’s rated speed, increase the maximum output frequency in E1-04 in programming
mode after autotuning.
It is possible to make user-defined V/f pattern settings (E1-04 through E1-10) in open-loop vector control
mode. (The preset V/f patterns cannot be selected.)

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

during

Opera-

tion

Setting

Range

Unit

Factory

Setting

Open Loop

Vector

Flux Vector

E1-04

Max. output
frequency

40.0 to

400.0

Hz

60.0

Q

Q

E1-05

Max. voltage

0.0 to 255.0

*1

VAC

200.0

*1

Q

Q

E1-06

Base frequency

0.0 to 400.0

Hz

60.0

Q

Q

E1-07

Mid. output
frequency

0.0 to 400.0

Hz

3.0

*2

A

E1-08

Mid. output
frequency voltage

0.0 to 255.0

*1

VAC

11.0

*1 *2

A

E1-09

Min. output frequency

0.0 to 400.0

Hz

0.5

Q

A

E1-10

Min. output
frequency voltage

0.0 to 255.0

*1

VAC

2.0

*1 *2

A

E1-13

Base voltage

0.0 to 255.0

VAC

0.0

Q

Q

* 1. These voltages are for 200 V class Inverters; double the voltage for 400 V class Inverters.
* 2. The default setting depends on the Inverter’s capacity. The default settings shown in the table

are for 200 V class, 0.4 to 1.5 kW Inverters. (See page NO TAG.)

Note 1.The default settings for E1-07 through E1-10 depend on the control method. The default

settings shown in the table are for open-loop vector control. (See page NO TAG.)

2. The four frequency settings must satisfy the following formula:

E1-04 (F

MAX

)

t E1-06 (F

A

) > E1-07 (F

B

)

t E1-09 (F

MIN

)

3. When making the V/f characteristics a straight line, set the same value in E1-07 (middle

output frequency) and E1-09 (minimum output frequency). In this case, constant E1-08
(middle output frequency voltage) will be disregarded.

4. If E1-13 is set to 0.0, the same value as in E1-13 will be set for E1-05. It does not normally

need to be set separately.

7

Advertising