User Constants

8.2.7 Protection Constants: L

- 28

J

Fault Restart: L5

Constant

Name

Setting

Factory

Change

during

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

g

during

Opera-

tion

Open Loop

Vector

Flux Vector

Page

L5-01

Number of auto re-
start attempts

Sets the number of auto restart at-
tempts.
Automatically restarts after a fault

0 to 10

0

B

B

- 56

L5 01

Num of Restarts

Automatically restarts after a fault
and conducts a speed search from
the run frequency.

0 to 10

0

B

B

- 56

L5-02

Auto restart operation
selection

Sets whether a fault contact output
is activated during fault restart.
0: Not output (Fault contact is not

activated )

0 1

0

B

B

- 56

L5 02

Restart Sel

activated.)

1: Output (Fault contact is acti-

vated.)

0 1

0

B

B

- 56

J

Torque Detection: L6

Constant

Name

Setting

Factory

Change

during

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

g

during

Opera-

tion

Open Loop

Vector

Flux Vector

Page

L6-01

Torque detection
selection 1

0: Overtorque detection disabled.
1: Detection during speed agree

only/Operation continues after
detection (Minor fault)

2: Detection during run/Operation

continues after detection (Minor
fault)

0 to 4

0

B

B

- 56

L6 01

Torq Det 1 Sel

fault)

3: Detection during speed agree

only/Inverter output is shut off
after detection (Fault)

4: Detection during run/Inverter

output is shut off after detection
(Fault)

0 to 4

0

B

B

- 56

L6-02

Torque detection level
1

Vector control: Motor rated torque
is set as 100%

0 to 300

150

B

B

- 56

L6 02

Torq Det 1 Lvl

is set as 100%.

0 to 300

150

B

B

- 56

L6-03

Torque detection time
1

Sets the torque detection time in
1-second units

0.0 to

10 0

0.1

B

B

- 56

L6 03

Torq Det 1 Time

1-second units.

10.0

0.1

B

B

- 56

L6-04

Torque detection
selection 2

Setting procedure is the same as for
“Torque detection selection 1”

0 to 4

0

A

A

- 56

L6 04

Torq Det 2 Sel

“Torque detection selection 1”
(L6-01 to L6-03.)

0 to 4

0

A

A

- 56

L6-05

Torque detection level
2

(

)

The following outputs are possible:
Torque detection selection 1:
Multi function output “Torque

0 to 300

150

A

A

- 56

L6 05

Torq Det 2 Lvl

Multi-function output “Torque
detection selection 1” NO/NC

0 to 300

150

A

A

- 56

L6-06

Torque detection time
2

detection selection 1 NO/NC
Torque detection selection 2:
Multi-function output “Torque
detection selection 2” NO/NC

0.0 to

10 0

0.1

A

A

- 56

L6 06

Torq Det 2 Time

detection selection 2” NO/NC

10.0

0.1

A

A

56

8