8.2

Programming Mode Constants

- 25

Constant

Number

Page

Control Methods

Change

during

Opera-

tion

Factory

Setting

Setting

Range

Description

Name

Constant

Number

Page

Flux Vector

Open Loop

Vector

Change

during

Opera-

tion

Factory

Setting

Setting

Range

Description

Display

H5-05

Communication error
detection selection

Set whether or not a communica-
tions timeout is to be detected as a
communications error.

0 1

1

A

A

----

H5 05

Serial Flt Dtct

0: Do not detect.
1: Detect

0 1

1

A

A

----

8.2.7 Protection Constants: L

J

Motor Overload: L1

Constant

Name

Setting

Factory

Change

during

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

g

during

Opera-

tion

Open Loop

Vector

Flux Vector

Page

L1-01

Motor protection
selection

Sets whether the motor overload
function is enabled or disabled at
electric thermal overload relay.
0: Disabled
1: Enabled

In some applications when the
Inverter power supply is turned
off, the thermal value is reset, so

0 1

1

B

B

- 48

L1 01

MOL Fault Select

off, the thermal value is reset, so
even if this constant is set to 1,
(Enabled), protection may not be
effective.
When several motors are con-
nected to one Inverter, set to 0
(Disabled) and ensure that each
motor is installed with a protec-
tion device.

0 1

1

B

B

- 48

L1-02

Motor protection time
constant

Sets the electric thermal detection
time in seconds units.

Usually setting is not necessary.

The factory setting is 150% over-
load for one minute.

0.1 to

5 0

1.0

B

B

- 48

L1 02

MOL Time Const

load for one minute.
When the motor’s overload re-
sistance is known, set at the
overload resistance when the
motor is hot started.

5.0

1.0

B

B

- 48

J

Power Loss Ridethrough: L2

Constant

Name

Setting

Factory

Change

during

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

g

during

Opera-

tion

Open Loop

Vector

Flux Vector

Page

L2-01

Momentary power
loss detection

0: Disabled (Undervoltage fault

detection)

1: Enabled (Restarted when the

power returns within the time
for L2-02. When L2-02 is ex-
ceeded, undervoltage fault
detection )

0 to 2

0

B

B

- 49

L2 01

PwrL Selection

detection.)

2: Enabled while CPU is operat-

ing. (Restarts when power re-
turns during control operations.
Does not detect undervoltage
fault.

0 to 2

0

B

B

- 49

L2-02

Momentary power
loss ridethru time

Sets the recovery time, when mo-
mentary power loss selection
(L2-01) is set to 1 in units of one

0.0 to

2 0

0.7

*1

B

B

- 49

L2 02

PwrL Ridethru t

(L2-01) is set to 1, in units of one
second.

2.0

*1

B

B

- 49

L2-03

Min. baseblock time

Sets the Inverter’s minimum base-
block time in units of one second,
when the Inverter is restarted after
power loss ridethrough.

Sets the time for the motor’s re-

0.0 to

0.5

B

B

50

L2-03

PwrL Baseblock t

Sets the time for the motor s re-

sidual voltage to dissipate.
When an overcurrent occurs
when starting a speed search or
DC injection braking, increase
the set values.

0.0 to

5.0

0.5

*1

B

B

- 50